PSS EVE0105 A-(en) VAC D300 19
Additional Inputs / Outputs:
Position feedback 4...20 mA - Code 4/20
(Options for electronics family BIA 637 per FM 3003731,
CSA 1001984 and CSA 1001988)
Stroke / angle derived from positioner feedback
1 output analog, galvanically separated, two-wire system
according to DIN 19234, for external supply
supply voltage ...........DC8to36V
1) 2)
signal range ...........3.8to21.5mA
0 % and 100 % configurable
device fault ............<1mA
Terminals for AI1 .......31+,32-
1 binary alarm output, galvanically separated, two-wire
system, according to DIN 19234, for external supply
supply voltage .........external,DC8to36V
1) 2)
Logic ................noalarm . . .< 1mA
alarm .....>2.2mA
device fault < 50 µA
Terminals for AB1.......81+,82-
The binary output for Alarm will be activated in the following
cases:
- Remaining control deviation
- Circuit to I/P module is disturbed
- Circuit to potentiometer is disturbed
- Calibration error:
- no angle calibration
- no current calibration
- Autostart failed
(These pre-settings can be configured via communication)
Electrical classification:
(Electronics family BIA 637)
see Certificate of Conformity EX EVE0105 A
Type of protection "intrinsic safety"
(Electronics family per FM 3003731)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection FM "non-incendive"
(Electronics family per FM 3003731)
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA "intrinsic safety"
(Electronics family per CSA 1001984 and CSA 1001988)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
*) Under development
1) Other values in hazardous areas
2) On request we can specify higher voltage limits
3) Operating mode min. (= low) / max. (= high)
selectable by adjustment of switch vanes
4) Data measured according to VDI/VDE 2177
5) With stroke 30 mm and lever length 90 mm
Additional Inputs / Outputs:
Built-in Limit Switch-Code S
(Options for electronics family BIA 637 per FM 3003731,
CSA 1001984 and CSA 1001988)
Inductive Limit Switch
- standard version (SJ2-N) .......Option STD
- security version (SJ2-SN) ......Option SEC
- Microswitches...............Option MIC*
Stroke / angle derived from positioner feedback,
two-wire system
Output.................2inductiveproximitysensors
acc. to DIN 19 234 or NAMUR for connection to switch-
ing amplifier
3)
Current consumption
vaneclear ............>2.2mA
vaneinterposed........<1mA
for control circuit with the following electrical values:
supplyvoltage .........DC8V,R
i
approx. 1 kOhm
supply voltage range....DC5to25V(onlywithZZZ)
residual ripple ..........<10%p.p.
permissible
lineresistance .........<100Ohms
Response characteristic
4) 5)
switching differential .....<1%
switching point repeatability .....<0.2%
Terminals for GW1........41+,42-
GW2........51+,52-
Electrical classification:
(Electronics family BIA 637)
see Certificate of Conformity EX EVE0105 A
Type of protection FM "intrinsic safety"
(Electronics family per FM 3003731)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection FM "non-incendive"
(Electronics family per FM 3003731)
Class I, Div. 2, Groups A, B, C, D, F, G;
hazardous locations indoor and outdoor, NEMA Type 4X
Type of protection CSA "intrinsic safety"
(Electronics family per CSA 1001984 and CSA 1001988)
Class I, Div. 1, Groups A, B, C, D;
hazardous locations indoor and outdoor, NEMA Type 4X *)
Built-in Pressure sensors, Code Option - SD*)
For supply air and output y1 to actuator
Measuringrange.........0to8bar(0to120psig)
Accuracy ...............0.5%
Temperature influence .....0.5%/10k(-4 0to80ºC)(-40 to176ºF)