SPA 1500
Installation instructions
96106-000-IN Installation instructions.doc
Page 5 of 9
Public Address and Alarm System
Public Address and Alarm System equipment shall be located above deck level as follows:
Loudspeakers: 2 – 3 m
Beacons: Max, 3 m.
Loudspeakers shall not be located above suspended ceilings or behind obstructions, which will
prevent free space sound distribution.
Loudspeakers shall be installed on brackets, which allow for future adjustments as follows:
At the horizontal plane: 180°
Downwards: 90° from the vertical plane.
8 INSTALLATION OF CABLES
8.1 Overall Installation Instructions
General
Installation of cables including, but not limited to, pulling, fixing, termination and testing shall
be performed in accordance with the documentation for this Project.
Cable splicing shall be avoided.
Any deviations discovered shall be reported to the responsible Construction Manager.
Do not use cables in connection with other systems. This to prevent disturbance and noise
caused by interference.
Pulling
The cable tail shall have sufficient service length in order to allow the cable to run via the top
of the cabinet and terminated at the bottom, or the other way, depending on bottom or top
entry. For a 2 meters high cabinet typical service length is 4 meters.
The cable installation shall be in accordance with procedures given by the Manufacturer of
each of the different cable types.
Fixing
The below recommendations shall be superseded by the Manufacturer’s recommendation, if
any.
When entering a Cabinet or Junction Box the cable shall be clamped no more than 10x the
cable diameter from the gland.
Clamps shall be of non-corrosive material, without sharp edges against the cable. Plastic cable
clamps shall be approved for ships environments, if used.
Cable clamps shall not be tightened in any way so that the cable can be damaged.
Termination, Marking and Labelling
Termination facilities shall be designed to give safe and secure connections for wires and cable
cores.
Regulations regarding segregation, material, sizing, colour coding, marking, etc. shall be
followed.
Adequate space shall be allowed for to give the installation a neat appearance. Sufficient access
for maintenance shall always be a major requirement for termination systems.
The cables shall be stripped as close as possible to the terminal block. Special care shall be
taken when removing the outer sheet to prevent the cores from being damaged. For armoured
cables the armour shall be removed at the cable entry.