l The communication via the IIC bus interface is only used
for default scaling and for service purposes.
l The repair time (exchange of the measuring system) after a
fail-safe error is eight hours (MTTR = 8 h)
l In the mode with the lowest demand rate, the reaction time
of a connected control and processing unit to dangerous
detectable errors is max. 1 hour.
If the demand rate is only once a year, then the measuring
system can be used as safety-relevant subsystem in "low
demand mode" (IEC 61508-4, 3.5.12).
If the ratio of the internal diagnostics test rate of the measuring
system to the demand rate exceeds the value 100, the
measuring system can be treated in the way it is executing a
safety function in the mode with low demand rate (IEC 61508-2,
7.4.3.2.5).
Corresponding characteristics is the value PFD
avg
(average
Probability of dangerous Failure on Demand). It is dependent
on the test interval T
Proof
between the function tests of the
protective function.
For number values see paragraph "Safety-technical charac-
teristics".
If the "low demand rate" does not apply, the measuring system
as safety-relevant part system in "high demand mode" should
be used (IEC 61508-4, 3.5.12).
The fault tolerance time of the complete system must be higher
than the sum of the reaction times or the diagnostics test
periods of all components in the safety chain.
Corresponding characteristics is the value PFH (failure rate).
For number values see paragraph "Safety-technical charac-
teristics".
A safe failure exists if the measuring system goes to the
dened safe condition without being required by the process or
the interference current outputs "Fail low" or "Fail high".
If the internal diagnostics system detects an error, a fault
current of < 2.3 mA will be outputted.
A dangerous undetected failure exists if the measuring system
switches neither to the dened safe condition, nor to failure
mode when the process requires it.
Low demand mode
High demand mode
Safe condition and fault de -
scription
Functional safety
28 OPTISWITCH 310 0 C - with two-wire output
29955-EN-060112