This is ensured by a controlled reaching of the response height
during lling. If lling up to the response height is not possible,
then a response of the measuring system must be triggered by
a suitable simulation of the level or the physical eect.
The methods and procedures used during the tests must be
stated and their suitability must be specied. The tests must be
documented.
If the function test proves negative, the entire measuring
system must be switched out of service and the process held
in a safe condition by means of other measures.
In the double channel architecture 1oo2D this applies
separately to both channels.
If the measuring system is used as overll protection, the proof
of the function is ensured by a simple function test which can
be triggered and monitored manually or by a connected control
system.
This function test is triggered by interrupting the supply cable
for at least two seconds, then a switch on procedure follows as
described in the operating instructions manual.
If the test is carried out this way, make sure that the vibrating
element is not covered.
If the evaluation is made by a control system, the correct
sequence of the current change must be checked and
documented.
If a connected signal conditioning instrument is used for
evaluation, the recurring function test can be carried out by
simply pressing the test key on the signal conditioning
instrument. You will nd more details in the operating
instructions manual of the signal conditioning instrument.
Suitable signal conditioning instruments are listed under
Technical data.
9.6 Safety-related characteristics
The failure rates of the electronics and the vibrating system
were determined by an FMEDA acc. to IEC 61508. Basis for
the calculations are component failure rates acc. to SN 29500.
All values relate to an average ambient temperature of +40°C
(+104°F) during operation. The calculations are further based
on the instructions stated in chapter "Planning".
Recurring function test when
using the measuring system
as overll protection
Functional safety
OPTISWITCH 3100 C - with two-wire output 31