DE3
CIRCUIT BREAKERS
01/15
DE3-22DE3-22DE3-22
PowerPact™ Circuit Breakers
H- and J-Frame Circuit Breakers
HD and HG 2 Pole
Thermal-Magnetic Trip Unit
H-Frame
Thermal-Magnetic Trip Unit
H-frame 150 A Thermal-magnetic CSA/UL Current-Limiting Circuit Breakers (600 V ac) with Factory SealedTrip Unit
Suitable for Rever se Connection ba
Current
Rating @
40° C
AC Magnetic
Trip Setting
D Interrupting G Interrupting J Interrupting L Interrupting
Terminal
Wire Range
Hold T rip
Catalogue
Number
Catalogue
Number
Catalogue
Number
Catalogue
Number
2-pole, 600 V ac 50/60 Hz
15 350 750 HDL26015 HGL26015 HJL26015 HLL26015
AL150HD
#14–#3/0 AWG
Cu or Al
20 350 750 HDL26020 HGL26020 HJL26020 HLL26020
25 350 750 HDL26025 HGL26025 HJL26025 HLL26025
30 350 750 HDL26030 HGL26030 HJL26030 HLL26030
35 400 850 HDL26035 HGL26035 HJL26035 HLL26035
40 400 850 HDL26040 HGL26040 HJL26040 HLL26040
45 400 850 HDL26045 HGL26045 HJL26045 HLL26045
50 400 850 HDL26050 HGL26050 HJL26050 HLL26050
60 800 1450 HDL26060 HGL26060 HJL26060 HLL26060
70 800 1450 HDL26070 HGL26070 HJL26070 HLL26070
80 800 1450 HDL26080 HGL26080 HJL26080 HLL26080
90 800 1450 HDL26090 HGL26090 HJL26090 HLL26090
100 900 1700 HDL26100 HGL26100 HJL26100 HLL26100
110 900 1700 HDL26110 HGL26110 HJL26110 HLL26110
125 900 1700 HDL26125 HGL26125 HJL26125 HLL26125
150 900 1700 HDL26150 HGL26150 HJL26150 HLL26150
3-pole, 600 V ac 50/60 Hz
15 350 750 HDL36015 HGL36015 HJL36015 HLL36015
AL150HD
#14–#3/0 AWG
Cu or Al
20 350 750 HDL36020 HGL36020
HJL36020 HLL36020
25 350 750 HDL36025 HGL36025 HJL36025 HLL36025
30 350 750 HDL36030 HGL36030 HJL36030 HLL36030
35 400 850 HDL36035 HGL36035 HJL36035 HLL36035
40 400 850 HDL36040 HGL36040 HJL36040 HLL36040
45 400 850 HDL36045 HGL36045 HJL36045 HLL36045
50 400 850 HDL36050 HGL36050 HJL36050 HLL36050
60 800 1450 HDL36060 HGL36060 HJL36060 HLL36060
70 800 1450 HDL36070 HGL36070 HJL36070 HLL36070
80 800 1450 HDL36080 HGL36080 HJL36080 HLL36080
90 800 1450 HDL36090 HGL36090 HJL36090 HLL36090
100 900 1700 HDL36100 HGL36100 HJL36100 HLL36100
110 900 1700 HDL36110 HGL36110 HJL36110 HLL36110
125 900 1700 HDL36125 HGL36125 HJL36125 HLL36125
150 900 1700 HDL36150 HGL36150 HJL36150 HLL36150
J-frame 250 A Thermal-magnetic (600 V ac) Factory Sealed Trip Unit Suitable for Reverse Connection ba
Current
Rating @
40° C
AC Magnetic
Trip Setting
D Interrupting G Interrupting J Interrupting L Interrupting R Interrupting
Terminal
Wire Range
Low High
Catalogue
Number
Catalogue
Number
Catalogue
Number
Catalogue
Number
Catalogue
Number
2-pole, 600 V ac 50/60 Hz
150 750 1500 JDL26150 JGL26150 JJL26150 JLL26150 AL175JD
#4–4/0 AWG
Al or Cu
175 875 1750 JDL26175 JGL26175 JJL26175 JLL26175
200 1000 2000 JDL26200 JGL26200 JJL26200 JLL26200
AL250JD
#3/0–350 kcmil
Al or
Cu
225 1125 2250 JDL26225 JGL26225 JJL26225 JLL26225
250 1250 2500 JDL26250 JGL26250 JJL26250 JLL26250
3-pole, 600 V ac 50/60 Hz
150 750 1500 JDL36150 JGL36150 JJL36150 JLL36150 JRL36150 AL175JD
#4–4/0 A WG
Al or Cu
175 875 1750 JDL36175 JGL36175 JJL36175 JLL36175 JRL36175
200 1000 2000 JDL36200 JGL36200 JJL36200 JLL36200 JRL36200
AL250JD
#3/0–350 kcmil
Al or
Cu
225 1125 2250 JDL36225 JGL36225 JJL36225 JLL36225 JRL36225
250 1250 2500 JDL36250 JGL36250 JJL36250 JLL36250 JRL36250
H- and J-frame T ermination Options
A-I-Line (see Section 5)
Plug-in
Draw out
Rear Connected
I-Line
®
F = No Lugs (includes terminal nut kit)
L = Lugs both ends
M = Lugs “ON” end Terminal Nut Kit “Off end
P = Lugs “OFF” end Terminal Nut Kit “On” end
N = Plug-inc
D=Drawoutc
S = Rear Connected c
b See catalogue for circuit breakers with field interchangeable trip units.
a For 100% rated circuit breakers, add a “C” in the 9th character place (for example, HDL36015C or JDL26150C). 100% rated circuit breakers have
copper lugs and can only be used with copper wire.
Circuit breakers with J, L, and R interrupting ratings are CSA/UL certified as current limiting.
c For N,D, and S details see page DE3-45, DE3-41
Class 611 / Refer to Catalog 0611CT1001
Interrupting Ratings (kA)
Voltage D G J L R
240 V 25 65 100 125 200
480 V 18 35 65 100 200
600 V 14 18 25 50 100