CIRCUIT BREAKERS
01/15
DE3-47
Micrologic™ Electronic Trip Units
Powerpact P- and R-Frame, and Masterpact Micrologic Electronic Trip Units
Standard
Trip Unit
Ammeter
Trip Unit
Power
Trip Unit
Harmonic
Trip Unit
Adjustable
Rating Plug
Pow erpact
®
circuit breakers may be specified with an y of the following
Micrologic Electronic Trip Units.
Micrologic (Standard) 3.0 and 5.0 Trip Units
• T
rue RMS sensing
• LI,
LSI trip configurations
• Field-interchangeab
le
long-time rating plugs
• LED
long-time pickup indication
• T
est kits available
• Ther
mal imaging
Micr
ologic (Ammeter) 3.0A, 5.0A and 6.0A Trip Units
Includes all features listed for Micrologic standard trip unit, as well as:
• LSIG
trip configurations
• Digital
ammeter—phase and neutral
• Phase
loading bar graph
• LED
trip indication
• Zone-selectiv
e
interlocking (ZSI) (short-time & ground-fault)
• Optional
Modb
us™ communications—PwerLogic
®
compatible
Micrologic (P o wer) 5.0P and 6.0P Trip Units
Pow er measurement and advanced protection features includes all features
listed
for Micrologic ammeter trip unit, as well as:
• LSI
trip configuration with programmable ground fault alarm
• LSIG
(Ground-fault trip) with programmable ground fault alarm
• Incremental
“fine
tuning” of L, S, I, and G pickup and delay settings
• LCD
dot matrix display and LED trip indication
• Adv
anced user interface
• Adv
anced protection IDMTL—selectable long-time delay bands
• Neutr
al protection
• P
ower measurement
• Contact
wear indication
• Modb
us communications—PowerLogic compatible
• Local
and remote settings
Micr
ologic (Harmonic) 5.0H and 6.0H Trip Units
Pow er quality measurement and adv anced protection features . Includes all
f
eatures listed for the Micrologic pow er trip unit, as well as:
• Enhanced
power measurements functions
• P
ower quality measurements
Adjustable Rating Plugs—Selection
To provide maximum design fle xibility, system protection, and field
upgradeability, each Micrologic
®
trip unit is equipped with an
interchangeable long-time rating plug. Each trip unit requires an adjustable
rating plug to determine the long-time pickup range of the circuit breaker .
These plugs are f actory-installed on ne w trip units, or can be ordered
separately for field-installable upgrades.
Adjustable rating plugs are offered in eight diff erent ranges of long-time
pickup adjustments. The following chart show the ranges of adjustments.
Each adjustment times the sensor rating (lr X In) of the circuit breaker sets
the long-time pickup value of the circuit breaker.
Long-time Pickup Settings
Rating
Plug
Long-time Pickup Settings
A 1.0 .90 .80 .70 .63 .60 .50 .45 .40
B 1.0 .95 .88 .75 .63 .56 .50 .44 .40
C 1.0 .95 .83 .75 .67 .56 .53 .50 .42
D 1.0 .95 .93 .90 .80 .70 .64 .48 .40
E 1.0 .95 .93 .90 .85 .80 .75 .70 .60
F 1.0 .98 .96 .94 .92 .90 .88 .86 .84
G .82 .80 .78 .76 .74 .72 .70 .68 .66
H .64 .62 .60 .58 .56 .54 .52 .50 .48
Micrologic Trip Units ✓ – Standard Feature o – Av ailable Option
Features
Standard Ammeter Power Harmonic
3.0 5.0 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H
LI ✓ ✓
LSI (Instantaneous can be turned off) ✓ ✓ ✓ ✓
LSIG / Ground-Fault Trip ✓ ✓ ✓
Ground-F ault Alarm (No Trip) ab ✓ ✓
Ground-F ault Alarm and Trip ab ✓ ✓
Adjustable Rating Plugs ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
True RMS Sensing ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
UL Listed ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Thermal Imaging ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Phase Loading Bar Graph ✓ ✓ ✓ ✓ ✓ ✓ ✓
LED for Long-time Pickup ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
LED for Trip Indication ✓ ✓ ✓ ✓ ✓ ✓ ✓
Digital Ammeter ✓ ✓ ✓ ✓ ✓ ✓ ✓
Zone-selective Interlocking ✓ ✓ ✓ ✓ ✓ ✓ ✓
Communications o o o ✓ ✓ ✓ ✓
LCD Dot Matrix Display ✓ ✓ ✓ ✓
Advanced User Interface ✓ ✓ ✓ ✓
Protective Relay Functions ✓ ✓ ✓ ✓
Neutral Protection a ✓ ✓ ✓ ✓
Contact Wear Indication ✓ ✓ ✓ ✓
Incremental Fine Tuning of Settings ✓ ✓ ✓ ✓
Selectable Long-time Delay Bands ✓ ✓ ✓ ✓
P o wer Measurement ✓ ✓ ✓ ✓
P o wer Quality Measurements ✓ ✓
W a v eform Capture ✓ ✓
a Requires neutral current transformer in 3Ø4W systems.
b Requires M2C or M6C Programmable Contact Module.
Micrologic Trip Unit and Options
Model Protection Additional Features
Field-Installable
Cat. No.c
Kit $ Price /
Circuit Breaker
$ Price Adder
2.0 (IEC only) LSO
None
S132R
3.0 (UL/ANSI only) LI S131A
5.0 LSI S133A
2.0A (IEC only) LSO
Ammeter
S142Rd
3.0A (UL/ANSI only) LI S141Ad
5.0A LSI S143Ad
6.0A LSIG S144Ad
5.0P LSI
Metering, Adv. Protection
S163Ade
6.0P LSIG S164Ade
5.0H LSI
Metering, Adv. Protection
&
Har
monic Analysis
S173Ade
6.0H LSIG S174Ade
c The standard rating plug supplied with a trip unit will be the “A” rating plug. To specify an
alternative adjustable rating plug, please add the letter designation to the end of the
catalog number. Please refer to page DE3-48 for a complete listing of adjustable settings
available with each plug. (Example: S143B would specify a “B” rating plug instead of the
standard "A" plug.) Use suffix “N” if no rating plug is required.
d When replacing
a standard trip unit with Type A (Ammeter), P (Power metering) or H
(Harmonic analysis) trip unit, order the 12-pin connector kit S33101 for the Masterpact NW
and NT and the PowerPact P-frame drawout circuit breakers or kit S33100 for PowerPact
P-frame and R-frame unit-mount and I-Line circuit breakers. See page DE3-48.
e Requires Circuit
Breaker Communications Module.
Special Options
Description Factory-Installed Suffix
Field-Installable
Cat. No.
Ship circuit breaker in closed position YK N/A
CT Characterization (Calibrated trip
system)
Q N/A
Class 612 / Refer to Catalog 0612CT0101
DE3_p047.fm Page 47 Saturday, January 10, 2015 2:45 AM