DE3
CIRCUIT BREAKERS
01/15
DE3-56
Circuit Breaker Enclosures
Enclosures
Circuit breaker enclosures are UL Listed, CSA Certified and are suitable for use as service entrance equipment, except
as footnoted. The short circuit current rating of an enclosed circuit breaker is equal to the interrupting rating at the supply
voltage marked on the circuit breaker installed, except as footnoted. Exceptions and restrictions are footnoted. Breakers
are ordered and shipped separately for field installation. For enclosure accessories, refer to page DE3-58.
a Enclosures with NRB or RB suffix have provisions for 3/4" through 2-1/2" bolt-on hubs in top endwall. Enclosures with R suffix have blank endwalls and
require field cut opening.
b Factory installed groundable neutral assembly includes (2) ground lugs and (2) neutral lugs. Equipment ground kit is also included.
c Accepts standard
rated 80% breakers. Not rated at 100%.
d Maximum short
circuit rating is 25 kAIR at 600 Vac, 65 kAIR at 480 Vac, 125 kAIR at 240 Vac.
e Earth Leakage
Module and Ground Fault Module are not compatible with these enclosures.
f Maximum short
circuit rating is 25 kAIR, 240 Vac.
g Order service
ground kit PKOGTA2 if required.
h Maximum short
circuit rating is 18 kAIR, 480 Vac and 240 Vac.
i Copper wire
only.
j When using
a CT in the M800S and R enclosure the unit will no longer accommodate a 200% neutral solution.
k CE certified per IEC60439-1, IP20D, PE type TN-C or TN-S
l Accepts MGL
or MJL standard rated (80%) breakers. Accepts PGL, PJL or PLL circuit breakers rated 80% (1200 A maximum) or
100% rated breakers, (800A maximum).
m CE certified per IEC60439-1, IP24D, PE type TN-C or TN-S
n Suitable
for rainproof Type 3R application by removing drain screw from bottom endwall.
o CE certified per IEC60439-1, IP56, PE type TN-C or TN-S
p NEMA 7—Indoor
Hazardous Locations—Division 1 and 2, Class I, Groups C and D; Class II, Groups E, F,and G; Class III.
q 80% rated circuit breakers only; SCCR 65 kA @ 240 Vac, 25 kA @ 480 Vac, 18 kA @ 600 Vac.
r Not UL Listed due to wire bending space.
s NEMA 9—Indoor
Hazardous Locations—Division 1 and 2, Class II, Groups E, F,and G; Class III.
t Has a tapped 2-1/2 in. conduit opening on top and bottom end wall
u Short circuit
current rating is 30 k AIR at 480 Vac.
v J250SS and
M800SS are 316 Grade Stainless Steel Circuit Breaker Enclosures. Type 316 stainless steel circuit breaker enclosures offer superior
corrosion resistance to a wider range of chemicals than Type 304 stainless steel enclosures. Type 316 better resists chloride and is often used in marine,
waste treatment and transportation applications.
w cULus marked
enclosure. For factory installed viewing window, add suffix VW. For enclosure suitable for use as Service Equipment use Cat. No.
CL600NAWK (neutral SN1000MA will be factory installed and bonded)
Accessories ........................................ P
ageDE3-58
Dimensions......................................... P
ageDE3-58
Circuit Breaker Enclosures
Circuit Breaker Enclosure
Cat. No. Prefix Rating Poles Cat. No. Cat. No. Cat. No.
NEMA 1 Flush NEMA 1 Surface NEMA 3Ra
FAL, FHL 15-100 1, 2, 3 FA100F FA100S FA100RB
QBL, QDL, QGL, QJL 100-225
2, 3
Q23225NFC
b Q23225NSCb Q23225NRBCb
HDL,HGL,HJL, HLL 15-150
J250F
cde J250Scde J250Rcde
JDL, JGL, JJL, JLL 150-250
HDL 15–100 A 3 — HD100Sfgcei —
JDL 150–250 A 3 — JD250Sigfce —
LAL, LHL, Q4L 125-400 2, 3 LA400F LA400S LA400R
LAL 125–400 A 3 — LA400LSgit —
MGL, MJL, PGL, PJL, PKL,
PLL
300-800 2, 3 M800S
jk M800Rje
PGL, PJL, PKL, PLL* 600-1200 2, 3 P1200Sk P1200Re
NEMA 4, 4X, 5, 3, 3R
Stainless Steelu
NEMA 12/3R, 12K
With Knockouts (NEMA
12K)
Without Knockoutsn
(NEMA 12/3R, 5)
FAL, FHL 15-100 1, 2, 3 FA100DS FA100AWK
HDL,HGL,HJL, HLL 15-150
2, 3
J250DS
cde
J250SScde
J250AWKcde
JDL, JGL, JJL, JLL 150-250
LAL, LHL, Q4L 125-400 LA400DS LA400AWK
LDL, LGL, LJL, LLL, LRL 250-600
3
— L600AWKw
LGL, LLL, LRL 250-600 — L600AWKMC
MGL, MJL, PGL, PJL, PKL,
PLL
300-800
2, 3
M800DS
o
M800SSo
M800AWKo
PGL, PJL, PKL, PLL* 250-1200 P1200AWKo
Nema 7e Cast Aluminum Nema 9s Cast Aluminum
JDL, JGLeqr 150–250 A 2, 3 J225X J225Y
Class 610
DE3_p056.fm Page 56 Friday, January 23, 2015 12:16 AM