CIRCUIT BREAKERS
Micrologic™ Electronic Trip Units
Micrologic Standard
Trip Unit
Micrologic Ammeter and
Energy Trip Unit
PowerPact™ H-, J-, and L-Frame Micrologic™ Trip Units
PowerPact™ H-, J-, and L-frame molded case circuit breakers may be
specified with any of the following Micrologic Electronic Trip Units.
Micrologic Standard 3.2/3.3 Trip Units
• True RMS sensing
• LI, LSI trip configurations
• Field-interchangeable trip units
• LED long-time pickup and trip indication
• Test kits available
• Thermal imaging
Micrologic Ammeter 5.2A/5.3A/6.2A/6.3A Trip Units
Includes all features listed for Micrologic standard trip unit, as well as:
• Advanced user interface
• Neutral protection
• Incremental fine tuning of settings
• Up to 12 alarms
• Digital ammeter—phase and neutral (4-pole only)
• Phase loading bar graph
• Maintenance indicators including contact wear, number of operations,
operating hours, and load profiles
• Cause of trip information for troubleshooting assistance
• LCD Display
• Zone-selective interlocking (ZSI) (short-time & ground-fault)
• Optional Modbus™ communications—PowerLogic™ compatible
Micrologic Energy 5.2E/5.3E/6.2E/6.3E Trip Units
Includes all features listed for Micrologic ammeter trip unit, as well as:
• Ground-fault trip with programmable ground fault alarm (available on
6.2E/6.3E only)
• Power and energy measurement
• Power quality measurements
• Current demand and power demand measurements
Micrologic Trip Unitsf for PowerPact H-, J-, and
L-Frame Circuit breakers
x– Standard Feature o – Av ailable Option
Features
Standard Ammeter Energy
3.2/3/3 3.2S/3.3S 5.2A/5.3A 6.2A/6.3A 5.2E/5.3E 6.2E/6.3E
LI x
LSIa x x x
LSIG / Ground-Fault Tripb x x
Ground-F ault Alarm/Tripb x x
Current Setting Directly in Amperes x x x x x x
True RMS Sensing x x x x x x
UL Listed x x x x x x
Thermal Imaging x x x x x x
LED for Long-time Pickup x x x x x x
LED for Green “Ready” x x x x x x
Up to 12 Alarms Used Together x x x x
Digital Ammeter x x x x
Zone-selective Interlockingc x x x x
Communications o o o o o o
LCD Display x x x x
F ront Display Module FDM121 o o o o
Advanced User Interface x x x x
Neutral Protectionb x x x x
Contact Wear Indicationd x x x x
Incremental Fine Tuning of Settings x x x x
Load Profiled,e x x x x
P o wer Measurement x x
P o wer Quality Measurements x x
a The LSI with 3.2S/3.3S trip units have fixed short time and long time delays.
b Requires neutral
current transformer on the three-phase four-wire loads
c ZSI for H/J frames is only OUT. for L-frame ZSI is In and OUT.
d Indication available
using the communication system only.
e % of hours in 4 current ranges: 0–49%, 50–79%, 80–89%, and >90% In.
f DC not available with electronic trip units.
Micrologic Trip Unit Settings for H- and J-Frame
Model Trip Function Trip Unit Ampere Setting
Standard
LI 3.2
15-20-25-30-35-40-45-50-60
35-40-45-50-60-70-80-90-100
50-60-70-80-90-100-110-125-150
70-80-100-125-150-175-200-225-250
LSI 3.2S
15-20-25-30-35-40-45-50-60
35-40-45-50-60-70-80-90-100
50-60-70-80-90-100-110-125-150
70-80-100-125-150-175-200-225-250
Ammeter
LSI 5.2A
15–60
35–100
50–150
70–250
LSIG 6.2A
15–60
35–100
50–150
70–250
Energy
LSI 5.2E
15–60
35–100
50–150
70–250
LSIG 6.2E
15–60
35–100
50–150
70–250
Micrologic Trip Unit Settings for L-Frame
Model Trip Function Trip Unit Ampere Setting
Standard
LI 3.3
70-80-100-125-150-175-200-225-250
125-150-175-200-225-250-300-350-400
200-225-250-300-350-400-450-500-600
LSI 3.3S
70-80-100-125-150-175-200-225-250
125-150-175-200-225-250-300-350-400
200-225-250-300-350-400-450-500-600
Ammeter
LSI 5.3A
125–400
200–600
LSIG 6.3A
125–400
200–600
Energy
LSI 5.3E
125–400
200–600
LSIG 6.3E
125–400
200–600
Class 611 / Refer to Catalog 0611CT1001