DE3
CIRCUIT BREAKERS
01/15
DE3-39
PowerPact™ Circuit Breaker Accessories
Electrical Accessories
Electrical Accessories
Accessory Description Rated Voltage
H-, J-, and L-Frame M-, P-, and R-Frame
Factory-
Installed
Cat. Suffix
H- and J-Frame L-Frame
Factory
Installed
Cat. Suffix
Field-Installable
Cat. No.
Field-Installable
Cat. No.
Field-Installable
Cat. No.
Auxiliary and
Alarm Switches
(OF, SD, SDE)
H-, J-, L-, M-, P,
and R-Frame
Provides circuit
breaker contact
status.
Note:The location
of the accessory
in the circuit
breaker
determines its
function.
Standard
Min
Load =
10mA with
24V
1
auxiliary switch (OF) 1a1b AA S29450 S29450 AA S29450
2 auxiliary switch (OF) 2a2b AB 2x S29450 2x S29450 AB 2x S29450
3 auxiliary switch (OF) 3a3b AC — 3x S29450 AC 3x S29450
Alarm Switch (SD) 1a1b BC S29450 S29450 BC S29450
Overcurrent trip switch (SDE) 1a1b BD — S29450 BD S29450
Consisting of:
OF Switch — S29450 — — —
SDE Adapter — S29451 — — —
Alarm switch and Overcurrent trip switch BE — 2x S29450 BE 2x S29450
Consisting of:
OF Switch — 2x S29450 — — —
SDE Adapter — S29451 — — —
Auxiliary Switch/Alarm Switch/Adapter
(OF/SD/SDE)
Kit
— — — — S33801b
Lo
w Level
Min
Load =
1mA with
24V
One
auxiliary switch (OF) 1a1b AE S29452 S29452 AE S29452
Two auxiliary switches (OF) 2a2b AF 2x S29452 2x S29452 AF 2x S29452
3 auxiliary switches (OF) 3a3b AG — 3x S29452 AG 3x S29452
Alarm Switch (SD) 1a1b BH S29452 S29452 BH S29452
Overcurrent trip switch (SDE) 1a1b BJ — S29452 BJ # S29452
Consisting of:
OF Switch — S29452 — — —
SDE Adapter — S29451 — — —
Alarm switch and Overcurrent trip switch
BK — 2x S29452 BK# 2x S29452
Consisting of:
OF Switch — 2x S29452 — — —
SDE Adapterc — S29451 — — —
Shunt Trip (MX)
Trips the circuit breaker from a
remote location by means of a trip
coil energized from a separate
supply voltage circuit.
AC
24 SK S29384 S29384 SK S33659
48 SL S29385 S29385 SL S33660
110-130 SA S29386 S29386 SA S33661
220-240 — — — SC S33662
208-277 SD S29387 S29387 SD S33663
380-480 SH S29388 S29388 SH S33664
525-600 SJ S29389 S29389 — —
DC
12 SN S29382 S29382 SN S33658
24 SO S29390 S29390 SK S33659
30 SU S29391 S29391 SK S33659
48 SP S29392 S29392 SL S33660
60 SV S29383 S29383 SL S33660
125 SR S29393 S29393 SA S33661
250 SS S29394 S29394 SC S33662
Undervoltage Trip (MN)
Instantaneously opens the circuit
breaker when the under-voltage
trip supply voltage drops to a value
between 35% and 70% of its rated
voltage . Closing is allowed when
the supply voltage of the
undervoltage trip reaches 85% of
rated voltage.
AC
24 UK S29404 S29404 UK S33668
48 UL S29405 S29405 UL S33669
110-130 UA S29406 S29406 UA S33670
220-240 — — — UC S33671
208-277 UD S29407 S29407 — —
380-480 UH S29408 S29408 UH S33673
525-600 UJ S29409 S29409 — —
DC
12 UN S29402 S29402 — —
24 UO S29410 S29410 UK S33668
30 UU S29411 S29411 UK S33668
48 UP S29412 S29412 UL S33669
60 UV S29403 S29403 UL S33669
125 UR S29413 S29413 UA S33670
250 US S29414 S29414 UC S33671
Undervoltage trip with externally
mounted adjustable time delay
unit for UVR of 0.5, 0.9, 1.5, 3.0
seconds before circuit breaker
trips
AC/DC
48 — S33680 S33680 — S33680a
100-130 — S33681 S33681 — S33681a
220-250 — S33682 S33682 — S33682a
380-480 — — — — S33683a
Undervoltage trip with externally
mounted
non-adjustab
le time
delay unit of 0.25 sec before circuit
breaker trips.
AC/DC
48 — S29426 S29426 — —
100-130 — — — — S33684a
200-250 — — — — S33685a
220-240 — S29427 S29427 — —
a Field-installable
kit
includes time delay module only. Order undervoltage trip separately.
b P-frame drawout
circuit breaker only.
c SDE Adapter used for H- and J-frame only.
d Not available on electrically operated P-frame.
Class 0611, 612 / Refer to Catalogs 0611CT1001, 0612CT0101
DE3_p039.fm Page 39 Saturday, January 10, 2015 2:32 AM